Power source for emergency lighting AESATM 10-60kVA, AESATT 10-80kVA

The power sources Aunilec ensure the highest protection and maximum quality of energy for all charges, including for industrial, security systems, electro-medical systems, industrial processes and telecommunications.

According to EN 50171 / NFC 71815 standards.

More details

Applications

Industrial UPSIndustrial UPS telecomIndustrial UPS for healthcare applicationIndustrial UPS for security systems

High efficiency & reliable power protection for emergency lighting

  • 1H standard autonomy. (1H30 or 3H on request)
  • Battery with long lifetime for more security
  • High current for batteries recharge to 80% in less than 12H
  • Start panel with isolation controller in compliance with the EC20

Optimal protection with highest efficiency

The power sources Aunilec ensure the highest protection and maximum quality of energy for all charges, including for industrial, security systems, electro-medical systems, industrial processes and telecommunications.

The range AESA-TM / TT has an on-line double conversion technology (VFI) making it impossible to interrupt the power supply to the transformer output of the inverter as stipulated by the VFI-SS-111 classification and accordance with IEC EN 62040-3.

The range AESA-TM / TT consists of a three phase input and single phase output from 10 to 60 kVA and three phase input and output 10-80 with IGBT rectifier and input power correction factor.

Inverter with transformer: full galvanic isolation

The output isolation transformer on the inverter, inside the UPS cabinet, provides galvanic isolation for the critical load improving versatility in system application:

  • Power supply 400Vac Tri + N (three phase without neutral on request)
  • IT neutral regime for powering emergency lighting in accordance with the standard.
  • Battery Start
Onduleur industriel avec transformateur d'isolation galvanique

Intelligent battery care: best battery performances

The battery care system consists of several features to optimize the battery performances and operating life, for example:

• Dual level charging to reduce the charging time.

• Deep discharging protection to reduce the ageing.

• Temperature compensation.

• Automatic and Manual Battery test.

• Charge blocking system to reduce electrolyte consumption.

It can operate with Open Vented and VRLA, Gel, Ni-Cd batteries.

Onduleur industriel VEGA LCD display

Advanced communications

Advanced multi-platform communications for all operating systems and network environments : PowerShield monitoring and shutdown software included, with SNMP agent, for Windows operating systems 8, 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris, Linux, Novell and other Unix operating systems (IBM AIX on RS6000 PowerPC, HP UNIX, SUN Solaris INTEL, SUN Solaris SPARC, SCO OpenServer 5, SCO UnixWare, Silicon Graphics IRIX, DEC UNIX, Compaq Tru64 UNIX, Digital UNIX, BSD UNIX, NCR Unix, FreeBSD UNIX, Open VMS).

• The UPS is provided with a cable for direct connection to a PC (Plug and Play).

• Compatible with PowerNETGuard for remote monitoring.

• Double RS232 serial port.

• Communications slot for network adapter installation; EPO contact (Emergency Power Off) for switching off the UPS by remote emergency button.

• Remote display panel with graphic display.

AESA100TMAESA150TMAESA200TMAESA300TMAESA400TMAESA600TM
Nominal power (kVA)101520304060
Active power (kw)913,518273654
• Input
Input voltage380/400/415 Vac TRI+N
Permissible input voltage400V +20% / -25%
Input frequency50 or 60Hz
Permissible input frequency45-65Hz
Input power factor0,9 with input filter at nominal voltage
Flex power walk-in0-100% in 120 sec (selectable)
• DC parameters
Battery typeVRLA (Valve Regulated Lead Acid), Wet, Ni-Cd
Nominale battery voltage384Vdc or 396Vdc according to the model
End cell voltageSelectable from 1.65 to 1.90 V/cell (for VRLA / Wet cells)
DC ripple voltage< 1%
Temperature compensationAvailable
• Output
Inverter typeIGBT-based Sinewave PWM controlled
Output voltage220/230/240 Vac PH-N
Output voltage regulationfrom 210Vac to 242Vac
Output frequency50 or 60 Hz (Frequency Converter Mode selectable)
Static variation+/- 1%
Dynamic variation+/- 5% in 10ms
Output frequency regulation+/- 0,05% (on battery mode)
Voltage distortion THDV1% (typical), 2% (max)
Crest factor load capacity3:1 (compliant to IEC 62040-3)
Speed of frequency variation1 Hz/sec (settable from 0,1 to 3)
Overloads conditioons110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute (% of Nominal Load)
Short circuit current250% for 1 second in current limitation (% of Nominal Load)
Inverter efficiency (%)95%
• Physical parameters and standards
Dimensions LxPxH (mm)555x740x1400800x740x1400
Weight without batteries (kg)200220230270500440
Noise level at 1m60dB62dB
Operating temperature0 to +40°C
Relative humidity< 95% non-condensing
Altitude site< 1000m without derating
ColorDark Grey 7016
IP ratingIP20
Remote signalsDry contact (as standard)
Remote controlsEPO and Bypass (as standard)
CommunicationsDouble RS232 port + 2 slots for communications interface
Options for communicationsSNMP Adapter, Centralized Monitoring Software, Temperature control sensors,J-Bus/ModBus, ProfiBus, Additional programmable contacts
StandardsEN50171, NFC71815, IEC 62040-3, IEC 62040-2, IEC 62040-1-1, CE; IEC 62040-1-1, EN 50091-2, EN 60950, EN 60529
Classifications  as IEC62040-3(Voltage & Frequency Independent) VFI-SS-111
Cable entranceBottom
Storage temperature-25°C to +75°C

AESA

100TT

AESA

150TT

AESA

200TT

AESA

300TT

AESA

400TT

AESA

600TT

AESA

800TT

Nominal power (kVA)10152030406080
Active power (kw)913,51827365472
• Input
Input voltage380/400/415 Vac TRI+N
Permissible input voltage400V +20% / -25%
Input frequency50 or 60Hz
Permissible input frequency45-65Hz
Input power factor

> 0,9 with input filter at nominal voltage

Flex power walk-in0-100% in 120 sec (selectable)
• DC parameters
Battery typeVRLA (Valve Regulated Lead Acid), Wet, Ni-Cd
Nominale battery voltage384Vdc or 396Vdc according to the model
End cell voltageSelectable from 1.65 to 1.90 V/cell (for VRLA / Wet cells)
DC ripple voltage< 1%
Temperature compensationAvailable
• Output
Inverter typeIGBT-based Sinewave PWM controlled
Output voltage380/400/415Vac TRI or TRI+N
Output voltage regulationfrom 360Vac to 420Vac
Output frequency50 or 60 Hz (Frequency Converter Mode selectable)
Static variation+/- 1%
Dynamic variation+/- 5% in 10ms
Output frequency regulation+/- 0,05% (on battery mode)
Voltage distortion THDV1% (typical), 2% (max)
Crest factor load capacity3:1 (compliant to IEC 62040-3)
Speed of frequency variation1 Hz/sec (settable from 0,1 to 3)
Overloads conditioons110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute (% of Nominal Load)
Short circuit current250% for 1 second in current limitation (% of Nominal Load)
Inverter efficiency (%)95%
• Physical parameters and standards
Dimensions LxPxH (mm)555x740x1400800x740x1400
Weight without batteries (kg)228241256315335460540
Noise level at 1m60dB62dB
Operating temperature0 to +40°C
Relative humidity< 95% non-condensing
Altitude site< 1000m without derating
ColorDark Grey 7016
IP ratingIP20
Remote signalsDry contact (as standard)
Remote controlsEPO and Bypass (as standard)
CommunicationsDouble RS232 port + 2 slots for communications interface
Options for communicationsSNMP Adapter, Centralized Monitoring Software, Temperature control sensors,J-Bus/ModBus, ProfiBus, Additional programmable contacts
StandardsEN50171, NFC71815, IEC 62040-3, IEC 62040-2, IEC 62040-1-1, CE; IEC 62040-1-1, EN 50091-2, EN 60950, EN 60529
Classifications  as IEC62040-3(Voltage & Frequency Independent) VFI-SS-111
Cable entranceBottom
Storage temperature-25°C to +75°C