UPS MultiPlus DSP0.9 Hybrid MLT10-500kVA (3/3) & MLM10-30kVA (3/1)

New !

The MultiPlus DSP0.9 Hybrid is simultaneous powered by solar energy, grid and battery. It is the first UPS with “cash back guarentee”. 

UPS Eco friendly

More details

Applications

Application UPS industryApplication UPS datacenterApplication UPS IT serverAppliaction UPS HealthcareApplications UPS Home

Specifications

  • Hybrid function (optional/scalable)
  • On-line “double conversion” technology (VFI)
  • High efficiency > 94%
  • Cold start function
  • Output power factor 0,9
  • Output short circuit and overload protection
  • Emergency power off (EPO)
  • Big graphic LCD screen
  • Automatic battery test
  • High capacity charging current in the battery
  • Temperature compensated battery charging
  • 512 events memory (more than 46000 alarms)
  • 2 serial ports RS232 and dry contacts
  • Functionality remote control via Teamviewer
  • Split bypass input
  • Internal batteries up to 80kVA
  • Very small footprint
  • Up to 8 units in parallel
  • Relay contacts (programmable)

  • Option : SNMP card, MODBUS adaptators

Hybrid UPS Aunilec

EFM - Energy Flow Manager

Energy flow manager onduleur hybride aunilec
  • Web-based real-time status informations
  • Automatic optimization of the energy flow according to energy prices and weather forecast
  • Remote load control
  • Various working priorities (weekday, weekend, holiday)
  • Programmable according to customer profiles
  • Automatic free updates
  • 100% future-proof

The advantages

  1. Our hybrid technology automatically choose the most ecologic and economic solution to power your load.
  2. The first working priority is solar energy (free of charge) to return your investment costs.
  3. All unused energy is stored in batteries. (feed into the grid is in preparation)
  4. The intelligent controller offers real time status informations. The different energy flows can be setup according weather datas and/or customer profiles.
  5. The connected batteries protect you against power failure-blackout.
  6. As a conventional on-line UPS, it always offers full protection against any kind of power problems without any internal switching.

MultiPlus DSP0.9 Hybrid operation

The connected load is powerded by our MultiPlus DSP0.9H, online double conversion UPS with the latest technology. The prior energy comes from the solar panels installation. Our special charge regulator is connected to the DC part of the hybrid UPS. The grid is connected in parallel and only supplies the missing energy if the solar energy is not available (at night) or not strong enough (according weather conditions). Additionaly to the hybrid function, the intelligent controller gives you “real time” status informations. You simply need a device connected to internet to setup and monitor the different energy flows. According weather prognostics, customer profile and energy prices, the controller will choose the most economic solution.

Aunilec MultiPlus DSP0.9 Hybrid operation

Working principle

Aunilec MultiPlus DSP0.9 Hybrid working principle

MLM-MLT

DSP

10

MLM-MLT

DSP

15

MLM-MLT

DSP

20

MLM-MLT

DSP

30

MLT-

DSP

40

MLT-

DSP

60

MLT-

DSP

80

MLT-

DSP

100

MLT-

DSP

120

MLT-

DSP

160

MLT-

DSP

200

MLT-

DSP

250

MLT-

DSP

300

MLT-

DSP

400

Power (kVA)10152030406080100120160200250300400
• Input
Voltage380/400/415VAC 3phase +N, +/- 20% (415VAC + 15% - 25%)
Frequency50/60Hz selectable, +/- 10Hz
Power factor> 0,98
Harmonic current distortion< 5% (< 3% optional)
ProtectionBreaker, voltage and frequency tolerance, input power / input power factor
Bypass voltage380/400/415VAC 3phase +N, +/- 10%
Bypass protectionVoltage and frequency out of range, short circuit
• Output
Power factor0,9
Power (kW)913,5182736547290108144180225270360
Voltage380/400/415VAC 3phase +N, +/-1% (220/230/240VAC possible for 10-30kVA)
Frequency50Hz or 60Hz adjustable
ToleranceLine synchronized +/- 2%, battery mode +/-0,1% adjustable
Efficiencyup to 94%
Crest factor3:1
Overload protection100-125% 8min, 125-150% 60sec
Additional protectionshort circuit, voltage and current range
THD (at 100% linear load)< 3%
• Battery
TypeVRLA AGM/Gel or other types
Nominal voltage+/- 360VDC (2x30-12VDC)
Float or end of discharge DC voltage+/-405VDC, +/-300VDC
BatteryInternalExternal
ProtectionOvercharging, battery fuses, temperature compensation (in option)
Automatic testDayli, weekly (adjustable)
• General
StandardEMC/LVD/EMI - EN62040-1/2, EN60950
User interfaceMulti language graphical LCD
LCD informationsPhase to phase voltage and phase to phase to neutral voltage / current, power, frequency, crest factor
AdvancedAuto diagnostic, different maintenance alarms and calibration through RS232
Communication2x RS232 ports, 4 dry contacts (8 dry contacts in option)
InputGenerator contact and emergency power off
Genset kitUser programmable
SoftwareManagement software
Alarm200 events (time and date) / 500 events in option
ProtectionOver-temperature, over-current, over-temperature alarm
Temperature range0°C - 40°C
Protection degreeIP20 (IP54 optional)
Humidity / Altitude90% max without condensation / < 1000m
Accoustic noise≤ 56dB≤ 61dB≤ 64dB≤ 67dB≤ 72dB
Weight (kg)869298175182196218259480560650770
Dimensions (mm), HxDxW1037x398x8121437x513x8521797x882x7631797x1246x763
• Hybrid controller
Power5/10 kW (up to 10 uinits in parallel)
MPPT input270-640VDC
Input min/max Voc200VDC/750VDC
Efficiency≥ 97%
CommunicationRS232, 4 dry contacts, EPO, multi language graphical LCD
Dimensions HxDxW / Weight3Ux500x440mm/13kg (5kW), 4Ux500x440mm/17kg (10kw)