DC Power systems cabinets AUPUS C

AUPUS C DC power systems are robust, free convection cooled, N+1 redundant backup power solutions for critical infrastructure applications such as transmission and distribution substations, process industries and special communications. 

More details

Features

  • Convection cooling
  • Models for 24, 48, 60, 110, 125, 220 VDC
  • Max 19.2 kW output power
  • N+1 redundancy
  • Plus or Minus Grounded or Floating
  • Battery connection: 1 string with full current: MCB or MCCB
  • Load Distribution Modules as options:
  • 2-pole or 1-pole MCB, NH000/NH00, NH01, Diazed

Options: Battery LVD, Load LVD, extra battery connections, Temperature sensors, IP21, bottom entry cabling

Product description

AUPUS C DC power systems are robust, free convection cooled, N+1 redundant backup power solutions for critical infrastructure applications such as transmission and distribution substations, process industries and special communications. AUPUS C DC power systems consist of MRC-rectifiers, VIDI+ controllers, Connections for mains and battery and wide variety of load distribution...

General construction
CoolingNatural convection
ProtectionIP20, option IP21
Controller user interfaceDisplay and local control in front panel
CablingBehind front panel
CoulorFrame RAL 7037, door RAL 7035
DimensionsHeight: 2000mm, width: 600mm, depth: 600mm
Environment and standards
Operating temperature-20°C ... +45°C
Humidity max95% relative humidity, non-condensing
Altitude max2000 m above sea level
SafetyIEC/EN 60950-1
EMCEmissions: IEC/EN61000-6-4, immunity : IEC/EN 61000-6-2, harmonic current: IEC/EN 61000-3-2, voltage fluctuation and flicker: IEC/EN 61000-3-3
Options
IP21 drip water cover
Cable duct for bottom entry cables, assembled side of cabinet
NTC temperature sensor
Load LVD contactors, battery LVD contactors
Controllers: VIDI+ or VIDI+ I/O
Auxiliary controllers: VIDI-BM battery monitoring, VIDI-LVD low voltage disconnector driver
InputAUPUS C 24, AUPUS C 48, AUPUS C 60, AUPUS C 110, AUPUS C 220
AC-connection3 W + N + PE
Nominale voltage230 / 400 VAC
Range, full180-275 VAC
Range, reduced140-180 VAC
Frequency45 à 65 Hz
Internal protection16A MCB / rectifier module
Mains terminalTerminal blocks 10 mm2
AUPUS C 24-6.6AUPUS C 48-9.6AUPUS C 60-9.6AUPUS C 110-9.6AUPUS C 220-9.6
Nominal current10.2 A15.4 A
Maximum current13.8 A19.4 A
Inrush current per rectifier14.7 A18 A
Main switch40 A
Recommended mains fuse3 x 25 A
AUPUS C 24-13.2AUPUS C 48-19.2AUPUS C 60-19.2AUPUS C 110-19.2AUPUS C 220-19.2
Nominal current2x 10.2 A2x 15.4 A
Maximum current2x 13.8 A19.4 A
Inrush current per rectifier14.7 A18 A
Main switch2x 40 A
Recommended mains fuse2x (3 x 25 A)
OutputAUPUS C 24-6.6AUPUS C 48-9.6AUPUS C 60-9.6AUPUS C 110-9.6AUPUS C 220-9.6
Grounding+,- or floating+ or floating+ or floatingFloatingFloating
Nominal voltage24 VDC48 VDC60 VDC110 VDC220 VDC
Voltage range21-31 VDC42-58 VDC51-72 VDC97-132 VDC189-265 VDC
Ripple noise< 100 mVp-p
RectifiersMax 6
Maximum current275A @ 24V197A @ 48V161A @ 60V87A @110V43A @ 220V
Output current240A @ 27.5V177 @ 54.5V141A @ 68.1V78A @ 123.6V39A @ 220V
Power max.6.6 kW9.6 kW
Redundant power5.5 kW8.0 kW
Output terminalTerminal block 25 mm2
OutputAUPUS C 24-13.2AUPUS C 48-19.2AUPUS C 60-19.2AUPUS C 110-19.2AUPUS C 220-19.2
Grounding+,- or floating+, floating+, floatingFloatingFloating
Nominal voltage24 VDC48 VDC60 VDC110 VDC220 VDC
Voltage range21-31 VDC42-58 VDC51-72 VDC97-132 VDC189-265 VDC
Ripple noise< 100 mVp-p
RectifiersMax 12
Maximum current550A @ 24V394A @ 48V322A @ 60V174A @110V86.4A @ 220V
Output current480A @ 27.5V354@ 54.5V281A @ 68.1V156A @ 123.6V78A @ 220V
Power max.13.2 kW19.2 kW
Redundant power12.1 kW17.6 kW
Output terminalTerminal block 25 mm2
Battery connectionAUPUS C 24-6.6AUPUS C 48-9.6AUPUS C 60-9.6AUPUS C 110-9.6AUPUS C 220-9.6
battery breaker in system1 pc MCB
Optional breakersMax 2 MCBMax 1 MCB
Battery shelves23
Connexion batterieAUPUS C 24-13.2AUPUS C 48-19.2AUPUS C 60-19.2AUPUS C 110-19.2AUPUS C 220-19.2
battery breaker in system1 pc MCB
Optional breakersMax 2 MCBMax 1 MCB
Battery shelves23

Load distribution

(option)

AUPUS C 24-6.6AUPUS C 48-9.6AUPUS C 60-9.6AUPUS C 110-9.6AUPUS C 220-9.6
1-pole MCB, 2...63AMax 2x24 loadsMax 2x24 loadsMax 2x24 loadsN/AN/A
2-poles MCB, 2...63AMax 2x12loadsMax 2x12 loadsMax 2x12 loadsMax 2x12 loadsMax 1x12 loads
2-poles MCB, 2...63A + AUX or alarmMax 2x10 loadsMax 2x10 loadsMax 2x10 loadsMax 1x10 loadsMax 1x10 loads
1-pole NH000/00 fusesMax 2x12 loadsMax 2x12 loadsMax 2x12 loadsN/AN/A
2-pole NH000/00 fusesMax 2x6 loadsMax 2x6 loadsMax 2x6 loadsMax 1x6 loadsMax 1x6 loads
1-pole NH01 fusesMax 1x6 loadsMax 1x6 loadsMax 1x6 loadsN/AN/A
2-pole NH01 fusesMax 1x3 loadsMax 1x3 loadsMax 1x3 loadsMax 1x3 loadsMax 1x3 loads
2-pole Diazed fusesMax 2x8 loadsMax 2x8 loadsMax 2x8 loadsMax 1x8 loadsMax 1x8 loads
AUPUS C 24-13.2AUPUS C 48-19.2AUPUS C 60-19.2AUPUS C 110-19.2AUPUS C 220-19.2
1-pole MCB, 2...63AMax 2x24 loadsMax 2x24 loadsMax 2x24 loadsN/AN/A
2-poles MCB, 2...63AMax 2x12 loadsN/AN/AMax 1x12 loadsMax 1x12 loads
2-poles MCB, 2...63A + AUX or alarmMax 2x10 loadsN/AN/AMax 1x10 loadsMax 1x10 loads
1-pole NH000/00 fusesMax 2x12 loadsMax 2x12 loadsMax 2x12 loadsN/AN/A
2-pole NH000/00 fusesMax 2x6 loadsN/AN/AMax 1x6 loadsMax 1x6 loads
1-pole NH01 fusesMax 1x6 loadsMax 1x6 loadsMax 1x6 loadsN/AN/A
2-pole NH01 fusesMax 1x3 loadsN/AN/AMax 1x3 loadsMax 1x3 loads
2-pole Diazed fusesMax 2x8 loadsN/AN/AMax 1x8 loadsMax 1x8 loads