UPS IRIS+RT 6/10kVA (1/1)

The IRIS+RT is designed for IT server and datacenter applications. The multifunction LCD graphical display is reversible which allows to use the UPS on rack or tower.

Eco mode 

More details

Applications

Applications UPS DatacenterApplication UPS IT server

The IRIS+RT is designed for IT server and datacenter applications. The multifunction LCD graphical display is reversible which allows to use the UPS on rack or tower.

Specifications

  • On-line “double conversion” technology (VFI)
  • DSP (Digital Signal Processor) technology
  • Wide input voltage range (120-276V or 208-478V)
  • Wide frequency range 40-70Hz +/- 0,5Hz
  • Input power factor up to 0.99 and high output power factor 0.9
  • Parallel connection up to 4 units (N+1)
  • Rack/Tower with convertible display
  • Output power factor correction (PFC)
  • Battery DC cold start
  • Genset compatible
  • ECO-mode for energy saving
  • Self testing when UPS startup
  • Internal static and manual bypass
  • Adjustable amount of batteries : 16/18/20pcs
  • Common or separate battery in parallel mode
  • Backup-time indication on the display
  • Charging 1-10A
  • Fixation for tower and rackmount included
  • EPO contact (Emergency Power Off)
  • Intelligent management trought RS485 slot, USB
  • Included monitoring software
  • 2 years warranty (electronics)

  • Options: SNMP card, external maintenance bypass, galvanic isolation transformer, IRIS+RT version (3/1)

Convertible Rack / Tower

The multifunction graphical LCD display is reversible for Rack and Tower use.  

IRIS+RT rack/tower

Multifunction LCD graphical display

All informations important power and user informations are available on the display.

Parallel mode

Up to 4 IRIS+RT UPS systems can be connected in parallel to get maximum power capacity. Only one battery is necessary with the parallel mode.
 

6000VA10000VA
Power (kW)5,49
• Input
ConnectionL-N (single-phase), optional : 3L-N 4 wires (three-phase)
Nominal voltage220/230/240VAC, optional 380/400/415VAC (3/1)
Input voltage range120-276VAC (1/1), optional 208-478VAC (3/1)
Frequency40-70Hz +/- 5Hz
Power factor> 0,99
THDi≤ 3% at 100% non-linear load
Bypass voltage range (ECO mode)

Max. voltage +25% (+10%, +20% optional)

Min. voltage -45% (-20%, -30% optional)

Frequency range +/- 10%

• Output
Output connection2x IEC-C13
Voltage220/230/240VAC
WaveformPure Sine Wave
THD≤ 2% linear load and ≤ 5% non-linear load
Frequency50/60Hz +/- 0,1Hz
Voltage range+/- 1%
Crest factor3:1
Efficiency at 75-100% load> 92% (AC mode) / > 94% (battery mode) / > 97% (ECO mode)
• Battery (external)
Voltage16/18/20pcs - only external batteries (modules)
Charging current1-10A
Parallel systemsCommon or separate battery possible
• Protection
EventsOverload - temperature - short circuit - battery discharge - voltage spikes
Overload capability (normal mode)Load ≤ 110%: 3min, ≤125%: 30sec, ≤ 150%: 1sec, >150 : shutdown of the UPS
Overload capability (backup mode)Load ≤ 110%: 30sec, ≤125%: 1sec, ≤ 150%: 200ms, >150 : shutdown of the UPS
Overload capability (bypass)Input fuse 40AInput fuse 63A
• Indications
Acoustic signalsInterruption, battery discharge, overload, fault
LEDGrid, battery, bypass, working modes, battery discharges, overload, error
LCDVoltage, frequency, load %, battery voltage, temperature, remaining backup time
• Bypass
TypeInternal static (automatic) and manual bypass / External bypass optional
• Certificates
EMC protectionCE, EN/IEC 62040-2, EN/IEC 62040-1-1
Protection classIP20 (up to IP55 optional)
• Interface
StandardUSB, dry contacts, EPO, RS485 (1slot)
OptionalSNMP card / parallel card with centralized monitoring
• Dimensions
UPS, WxDxH, mm440x580x130mm (3U)
Weight of the UPS23kg25kg
• External battery modules
Battery20pcs per 12V/9Ah
Dimensions WxDxH and weight440x720x132 (3U) / 67kg
Connections input / output / battery modulesTerminals