Industrial UPS Série OP 5000-10000VA

The OP series consists of UPS 5000 VA to 10000 VA. The technology, On-Line Double Conversion, is able to guarantee a constant supply of private and any electrical interference, both in the presence or absence of voltage with the help of the battery. The management software allows monitoring, programming and supervision of the proper operation of powered devices. 

Eco mode

More details

Applications

Aunilec power solutions

Specifications

  • On-line double conversion technology programmable
  • Classification VFI-SS-112 according to EN50091-3
  • Sine wave output with THD < 3%
  • High efficiency mode selectable
  • Standard RS232 and USB port SNMP interface (slot avalaible)
  • Dynamic informations and conditions visualized on LCD display
  • “Shut down and reboot” management
  • ABM: Advanced Battery Management
  • Modem, LAN and FAX protection
  • “Green Mode” (Shuts down automatically in absence of load)
  • EPO - emergency shut down
  • Neutral correct conection test

LCD display informations

OUTPUT (voltage, frequency, load %, load W, load VA, current A)

INPUT (voltage, frequency)

BATTERY (voltage, autonomy, load %, amout battery pack connected)

GENERAL (temperature, CPU, model UPS VA, language choice)

It is always possible to program parameters and functions displayed on the LCD screen.

Communications

Communication between the UPS and connected equipment can be made through :

• SNMP protocol (optional)

• USB port

• RS232 port

• Relay card AS400 (optional)

OP series - On-line Double Conversion

The OP series consists of UPS 5000 VA to 10000 VA. The technology, On-Line Double Conversion, is able to guarantee a constant supply of private and any electrical interference, both in the presence or absence of voltage with the help of the battery. The management software allows monitoring, programming and supervision of the proper operation of powered devices. UPS OP series are particularly suitable for powering computer system networks (industrial automation, telecommunications ...). The study of the battery also drew our attention because it is one of the most fundamental parts of the UPS. Indeed, we have developed an innovative charging system ABM (Advanced Battery Management) which increases the lifetime of the battery and optimizing recharge time (3-level charging technology).

Functions et protections

The OP series is capable of supporting the following electrical problems :

• General shutdown

• Undervoltage

• Electrical fault

• Overvoltage

• Frequency variation

• Micro-breaks

• Harmonic distortion in network

OP5000OP6000OP8000OP10000OP8000TOP10000T
• General
Power (VA)50006000800010000800010000
Power (W)350042005600700056007000
TechnologyON-LINE double conversion programmable with automatic By-Pass and High Efficiency Mode
ClassificationVFI-SS111 according to EN62040-3
• Input
Nominal voltage (Vac)208-220-230-240 (Ph+N)360-380-400-415 (TRI+N)
Voltage range (Vac)160-276311-477
Nominal frequency (Hz)50-60 auto sensing
Frequency range+/-2%, +/-5%, +/-7% selectable
Power factor> 0,98
• Output
Nominal voltage (Vac)208-220-230-240 selectable
Voltage range (Vac)+/-2%
Wave typesine wave
Nominal frequency (Hz)50-60 +/-0,5%
Static by-passyes, settable through  LCD
Manual by-passserial with cover protection
Efficiency> 95% in high efficiency mode
Auto power offautomatic turn off with no load “Eco mode”
Harmonic distortion< 3% THD with linear load
Crest factor3:1
AC restartUPS turns off due to low battery, turns on automatically when mains comes back
• Battery
Typeseal Lead-Acid Maintenance Free
Recharge time (90%)4 hours
Standard autonomy10 to 30 min (according to the load)
Autonomy expansionyes, optionnal with external battery cabinet (selectable through LCD)
Battery startingyes
ProtectionsBattery test, protection from deep discharge & battery replacement indication
• Protections
Overload125% for 60sec and 150% for 10sec
Shortcircuitwith fuse / circuit breaker
LANLan RJ45 (10BaseT)
• Norms
Safety / EMC complianceEN62040-1 / EN62040-2
Surge capacityEN61000-3
• Interface
DisplayInteractive LCD (voltage/frequency in/out, load%, temperature, output power VA / W, output current, autonomy left, battery voltage)
Communication Standard RS232 & Optoisolated contacts + USB
Smart slotYes, possibility to connect an internal SNMP or a AS400 cart (optional)
EPOyes contact avalaible
Languageselectable (IT, EN, DE, FR, ES)
SoftwareWindows 2000 - XP - 2003 - 2008 - Vista - 7 - Linux
• Environment
Working temperature0°C - 40°C
Relative humidity95% (without condensing)
Dimensions (LxPxH), mm260x590x580260x690x715     
Weight net / grass, kg86 / 106112 / 139