Industrial UPS VEGA 10-600kVA

Typical VEGA UPS design includes as standard splitted input and bypass line, inverter with transformer for total isolation  Input-Bypass-Output-Maintenance disconnectors, Backefeed protection for your network.

Eco mode

More details

Applications

Industrial UPSApplications UPS DatacenterApplication UPS IT serverIndustrial UPS telecomIndustrial UPS for healthcare applicationIndustrial UPS for security systems

High efficiency & reliable power protection for:

  • Datacenter and IT Systems
  • Industrial Applications
  • Medical, diagnostic and test devices
  • Bank and Finance applications
  • Emergency lighting EN50171 - NFC71815

Optimal protection with highest efficiency

Aunilec VEGA Series UPS is the top line in the power quality solutions for mission critical applications, including datacenters, industrial processes, building and medical emergency systems. From scalability to redundancy, from user-friendliness to maintainability, from parallel to connectivity, and from investment protection to lower cost of ownership, whichever value you need, VEGA provides industry leading efficiency. In fact has been carefully designed to deliver maximum Return On Investment (ROI) and MTBF ,with the quickest Mean Time To Repair (MTTR). VEGA is an online double conversion UPS (VFI SS 111 – IEC EN 62040-3) with isolated inverter. The VEGA Series range includes three-phase input and single-phase output versions from 10 to 100kVA with 6-Pulse thyristor rectifier (optional 12-Pulse for 60-80kVA) with and without optional input filter for harmonics-less distortion; from 10 to 200kVA three-phase input and output with 6-Pulse thyristor rectifier; from 100 to 600kVA three-phase input and output versions HP with IGBT Power Factor Correction rectifier.

Inverter with transformer: full galvanic isolation

The output isolation transformer on the inverter, inside the UPS cabinet, provides galvanic isolation for the critical load improving versatility in system application:

• Galvanic isolation for medical loads and special infrastructure.

• Two truly separate network inputs (main and emergency), coming from two different sources (with different neutrals); this is particularly well suited to parallel system in order to ensure selectivity between either sources, thus improving the reliability of the entire installation.

• Installation in networks without neutral.

Onduleur industriel avec transformateur d'isolation galvanique


Flexibility and dedicated solutions

VEGA Series has a flexible control which allows several operational configuration as On-Line or Normal Mode, Ecomode, Smart Active, Stand-by, Frequency Converter and Voltage Stabilizer. A broad range of accessories and options, complex configurations and system architectures can be achieved to guarantee maximum power availability and the option to add new UPS without interruption to existing users. Using the Aunilec UPS Group Synchronizer (UGS) and Parallel Systems Joiner (PSJ), sophisticated inter group parallel and redundant systems can be achieved to provide the highest possible levels of resilience and availability. VEGA UPS can be adapted to meet the most specific requirements. Contact Aunilec offices to discuss customized or dedicated solutions for your site.

Intelligent battery care: best battery performances

VEGA UPS battery care system consists of several features to optimize the battery performances and operating life, for example:

• Dual level charging to reduce the charging time.

• Deep discharging protection to reduce the ageing.

• Temperature compensation.

• Automatic and Manual Battery test.

• Charge blocking system to reduce electrolyte consumption.

VEGA can operate with Open Vented and VRLA, Gel, Ni-Cd batteries.

Onduleur industriel VEGA LCD display

Advanced communications

Advanced multi-platform communications for all operating systems and network environments : PowerShield monitoring and shutdown software included, with SNMP agent, for Windows operating systems 8, 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris, Linux, Novell and other Unix operating systems (IBM AIX on RS6000 PowerPC, HP UNIX, SUN Solaris INTEL, SUN Solaris SPARC, SCO OpenServer 5, SCO UnixWare, Silicon Graphics IRIX, DEC UNIX, Compaq Tru64 UNIX, Digital UNIX, BSD UNIX, NCR Unix, FreeBSD UNIX, Open VMS).

• The UPS is provided with a cable for direct connection to a PC (Plug and Play).

• Compatible with PowerNETGuard for remote monitoring.

• Double RS232 serial port.

• Communications slot for network adapter installation; EPO contact (Emergency Power Off) for switching off the UPS by remote emergency button.

• Remote display panel with graphic display.

VEGA-HP : Zero impact source

The VEGA-HP Series features the added advantages of the Zero Impact Source formula offered by an IGBT-based rectifier. Such eliminates problems related with installation in networks with limited power capacity, where the UPS is supplied by a generator set or anywhere there compatibility problems with loads generating current harmonics. VEGA-HP has very low input Total Harmonic Distortion in current, less than 3% in all load conditions and input Power Factor 0.99, plus the start-up delay function to restart the rectifier when mains power is really restored. Such input features provide saving cost in installation because smaller circuit protections devices, smaller electrical infrastructure (as genset and transformer) and less wiring size.

Maximum availability

Distributed or centralized parallel configuration of up to 8 units per redundant (N+1) or power parallel system. Parallel configurations between model with different power ratings are also possible. Hot System Expansion (HSE): allows the addition of a further UPS into an existing system, without the need to switch off the working UPS or transfer them to bypass mode. This guarantees maximum load protection, even during maintenance and system expansion. Efficiency Control System (ECS): a system to optimize the operating efficiency of parallel systems, according maximum levels of availability, even in the event of an interruption to the parallel bus cable: the system is ‘FAULT TOLERANT’. It is not affected by connections cable faults and continues powering the load without disruption, signaling an alarm condition.

VM010*VM015*VM020*VM030VM040VM060VM080VM100
Nominal power (kVA)10152030406080100
Active power (kw)913,5182736547290
• Input
Input voltage to rectifier380/400/415 Vac TRI
Input voltage to bypass380/400/415 Vac TRI+N
Permissible input voltage400V +20% / -25%
Input frequency50 or 60Hz
Permissible input frequency45-65Hz
Input power factor0,9 with input filter at nominal voltage
Flex power walk-in0-100% in 120 sec (selectable)
• DC parameters
Battery typeVRLA (Valve Regulated Lead Acid), Wet, Ni-Cd
Nominale battery voltage384Vdc or 396Vdc according to the model
End cell voltageSelectable from 1.65 to 1.90 V/cell (for VRLA / Wet cells)
DC ripple voltage< 1%
Temperature compensationAvailable
• Output
Inverter typeIGBT-based Sinewave PWM controlled
Output voltage220/230/240 Vac PH-N
Output voltage regulationfrom 210Vac to 242Vac
Output frequency50 or 60 Hz (Frequency Converter Mode selectable)
Static variation+/- 1%
Dynamic variation+/- 5% in 10ms
Output frequency regulation+/- 0,05% (on battery mode)
Voltage distortion THDV1% (typical), 2% (max)
Crest factor load capacity3:1 (compliant to IEC 62040-3)
Speed of frequency variation1 Hz/sec (settable from 0,1 to 3)
Overloads conditioons110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute (% of Nominal Load)
Short circuit current250% for 1 second in current limitation (% of Nominal Load)
Inverter efficiency (%)95%
• System parameters
UPS efficiencyup to 98% in ECO mode and Smart Active
• Physical parameters and standards
Dimensions LxPxH (mm)555x740x1400800x740x1400800x800x1900
Weight without batteries (kg)200220230270302440500580
Noise level at 1m60dB62dB
Operating temperature0 to +40°C
Relative humidity< 95% non-condensing
Altitude site< 1000m without derating
ColorDark Grey 7016
IP ratingIP20
Remote signalsDry contact (as standard)
Remote controlsEPO and Bypass (as standard)
CommunicationsDouble RS232 port + 2 slots for communications interface
Options for communicationsSNMP Adapter, Centralized Monitoring Software, Temperature control sensors,J-Bus/ModBus, ProfiBus, Additional programmable contacts
StandardsIEC 62040-3, IEC 62040-2, IEC 62040-1-1, CE; IEC 62040-1-1, EN 50091-2, EN 60950, EN 60529
Classifications  as IEC62040-3(Voltage & Frequency Independent) VFI-SS-111
Cable entranceBottom
Storage temperature-25°C to +75°C

* Available with internal batteries

VT010*VT015*VT020*VT030VT040VT060VT080
Nominal power (kVA)10152030406080
Active power (kw)913,51827365472
• Input
Input voltage to rectifier380/400/415 Vac TRI
Input voltage to bypass380/400/415 Vac TRI+N
Permissible input voltage400V +20% / -25%
Input frequency50 or 60Hz
Permissible input frequency45-65Hz
Input power factor> 0,9 with input filter at nominal voltage
Flex power walk-in0-100% in 120 sec (selectable)
• DC parameters
Battery typeVRLA (Valve Regulated Lead Acid), Wet, Ni-Cd
Nominale battery voltage384Vdc or 396Vdc according to the model
End cell voltageSelectable from 1.65 to 1.90 V/cell (for VRLA / Wet cells)
DC ripple voltage< 1%
Temperature compensationAvailable
• Output
Inverter typeIGBT-based Sinewave PWM controlled
Output voltage380/400/415 Vac TRI+N
Output voltage regulationfrom 360Vac to 420Vac
Output frequency50 or 60 Hz (Frequency Converter Mode selectable)
Static variation+/- 1%
Dynamic variation+/- 5% in 10ms
Output frequency regulation+/- 0,05% (on battery mode)
Voltage distortion THDV1% (typical), 2% (max)
Crest factor load capacity3:1 (compliant to IEC 62040-3)
Speed of frequency variation1 Hz/sec (settable from 0,1 to 3)
Overloads conditioons110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute (% of Nominal Load)
Short circuit current250% for 1 second in current limitation (% of Nominal Load)
Inverter efficiency (%)95%
• System parameters
UPS efficiencyup to 98% in ECO mode and Smart Active
• Physical parameters and standards
Dimensions LxPxH (mm)555x740x1400800x740x1400
Weight without batteries (kg)228241256315335460540
Noise level at 1m60dB62dB
Operating temperature0 to +40°C
Relative humidity< 95% non-condensing
Altitude site< 1000m without derating
ColorDark Grey 7016
IP ratingIP20
Remote signalsDry contact (as standard)
Remote controlsEPO and Bypass (as standard)
CommunicationsDouble RS232 port + 2 slots for communications interface
Options for communicationsSNMP Adapter, Centralized Monitoring Software, Temperature control sensors,J-Bus/ModBus, ProfiBus, Additional programmable contacts
StandardsIEC 62040-3, IEC 62040-2, IEC 62040-1-1, CE; IEC 62040-1-1, EN 50091-2, EN 60950, EN 60529
Classifications  as IEC62040-3(Voltage & Frequency Independent) VFI-SS-111
Cable entranceBottom
Storage temperature-25°C to +75°C

* Available with internal batteries

VT100VT120VT160VT200
Nominal power (kVA)100120160200
Active power (kw)90108144180
• Input
Input voltage to rectifier380/400/415 Vac TRI
Input voltage to bypass380/400/415 Vac TRI+N
Permissible input voltage400V +20% / -25%
Input frequency50 or 60Hz
Permissible input frequency45-65Hz
Input power factor> 0,9 with input filter at nominal voltage
Flex power walk-in0-100% in 120 sec (selectable)
• DC parameters
Battery typeVRLA (Valve Regulated Lead Acid), Wet, Ni-Cd
Nominale battery voltage396Vdc
End cell voltageSelectable from 1.65 to 1.90 V/cell
DC ripple voltage< 1%
Temperature compensationAvailable
• Output
Inverter typeIGBT-based Sinewave PWM controlled
Output voltage380/400/415 Vac TRI+N
Output voltage regulationfrom -8% to +10%
Output frequency50 or 60 Hz (Frequency Converter Mode selectable)
Static variation+/- 1%
Dynamic variation+/- 5% in 10ms
Output frequency regulation+/- 0,05% (on battery mode)
Voltage distortion THDV1% (typical), 2% (max)
Crest factor load capacity3:1 (compliant to IEC 62040-3)
Speed of frequency variation1 Hz/sec (settable from 0,1 to 3)
Overloads conditioons110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute (% of Nominal Load)
Short circuit current250% for 1 second in current limitation (% of Nominal Load)
Inverter efficiency (%)95%
• System parameters
UPS efficiencyup to 98% in ECO mode and Smart Active
• Physical parameters and standards
Dimensions LxPxH (mm)800x800x1900
Weight (kg)600610690790
Noise level at 1m65dB68dB
Operating temperature0 to +40°C
Relative humidity< 95% non-condensing
Altitude site< 1000m without derating
ColorDark Grey 7016
IP ratingIP20
Remote signalsDry contact (as standard)
Remote controlsEPO and Bypass (as standard)
CommunicationsDouble RS232 port + 2 slots for communications interface
Options for communicationsSNMP Adapter, Centralized Monitoring Software, Temperature control sensors,J-Bus/ModBus, ProfiBus, Additional programmable contacts
StandardsIEC 62040-3, IEC 62040-2, IEC 62040-1-1, CE; IEC 62040-1-1, EN 50091-2, EN 60950, EN 60529
Classifications  as IEC62040-3(Voltage & Frequency Independent) VFI-SS-111
Cable entranceBottom
Storage temperature-25°C to +75°C

VT

100HP

VT

120HP

VT

160HP

VT

200HP

VT

250HP

VT

300HP

VT

400HP

VT

500HP

VT

600HP

Nominal power (kVA)100120160200250300400500600
Active power (kw)90108144180225270360450540
• Input

Input voltage

to rectifier

380/400/415 Vac TRI
Input voltage to bypass380/400/415 Vac TRI+N
Permissible input voltage400V +20% / -25%
Input frequency50 or 60Hz
Permissible input frequency45-65Hz
Input THDI< 3%
Input power factor> 0,99
Flex power walk-in0-100% in 120 sec (selectable)
• DC parameters
Battery typeVRLA (Valve Regulated Lead Acid), Wet, Ni-Cd
Nominale battery voltage480Vdc
End cell voltageSelectable from 1.65 to 1.90 V/cell (for VRLA / Wet cells)
DC ripple voltage< 1% (RMS value)
Temperature compensationAvailable
• Output
Inverter typeIGBT-based Sinewave PWM controlled
Output voltage380/400/415 Vac TRI+N
Output voltage regulationfrom -8% to +10%
Output frequency50 or 60 Hz (Frequency Converter Mode selectable)
Static variation+/- 1%
Dynamic variation+/- 5% in 10ms
Output frequency regulation+/- 0,05% (on battery mode)
Voltage distortion THDV1% (typical), 2% (max)
Crest factor load capacity3:1 (compliant to IEC 62040-3)
Speed of frequency variation1 Hz/sec (settable from 0,1 to 3)
Overloads conditioons110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute (% of Nominal Load)
Short circuit current250% for 1 second in current limitation (% of Nominal Load)
Inverter efficiency (%)95%
• System parameters
UPS efficiencyup to 98% in ECO mode and Smart Active
• Physical parameters and standards
Dimensions LxPxH (mm)800x850x19001000x850x19001500x1000x19002100x1000x1900
Weight (kg)65670080091010001400170021002400
Noise level at 1m
63-68dB
70-72dB
Operating temperature0 to +40°C
Relative humidity< 95% non-condensing
Altitude site< 1000m without derating
ColorDark Grey 7016
IP ratingIP20
Remote signalsDry contact (as standard)
Remote controlsEPO and Bypass (as standard)
CommunicationsDouble RS232 port + 2 slots for communications interface
Options for communicationsSNMP Adapter, Centralized Monitoring Software, Temperature control sensors,J-Bus/ModBus, ProfiBus, Additional programmable contacts
StandardsIEC 62040-3, IEC 62040-2, IEC 62040-1-1, CE; IEC 62040-1-1, EN 50091-2, EN 60950, EN 60529
Classifications  as IEC62040-3(Voltage & Frequency Independent) VFI-SS-111
Cable entranceBottom
Storage temperature-25°C to +75°C