DC Power systems in 19" 12U Racks AUPUS C

AUPUS C DC power systems are robust, free convection cooled, N+1 redundant backup power solutions for critical infrastructure applications such as transmission and distribution substations, process industries and telecommunications.

More details

Features

  • Convection cooling
  • Models for 24, 48, 60, 110, 220 VDC
  • Max 8.0 kW output power
  • N+1 redundancy
  • Plus or Minus Grounded or Floating
  • Battery connection: 1 string with full current, MCB protection
  • Load Distribution Modules as options
  • 2-poles or 1-pole MCB

Options: Battery LVD, Load LVD, extra battery connections, Temperature sensors, IP21

Product description

AUPUS C DC power systems are robust, free convection cooled, N+1 redundant backup power solutions for critical infrastructure applications such as transmission and distribution substations, process industries and telecommunications. AUPUS C DC power systems consist of MRC-rectifiers, VIDI+ controllers, connections for mains and battery and load distribution MCB. 

General construction
CoolingNatural convection
ProtectionIP20, option IP21
Controller user interfaceDisplay and local control in front panel
Distribution and connectionsBehind front panel
ColorFrame RAL 7037, door RAL 7035
DimensionsHauteur: 533mm, largeur: 438mm, profondeur: 370mm
Environment and standards
Operating temperature-20°C ... +45°C
Humidity max95% relative humidity, non-condensing
Altitude max2000 m above sea level
SafetyIEC/EN 60950-1
EMCEmissions: IEC/EN61000-6-4, immunity : IEC/EN 61000-6-2, harmonic currents: IEC/EN 61000-3-2, voltage fluctuation and flicker: IEC/EN 61000-3-3
Others options
Wall mounting kit including IP21 drip water cover
NTC temperature sensor
Battery LVD contactors
Controllers: VIDI+ or VIDI+ I/O
InputAUPUS C 24, AUPUS C 48, AUPUS C 60, AUPUS C 110, AUPUS C 220
AC-connections3W + N + PE
Nominal voltage230 / 400 VAC
Range, full180-275 VAC
Range, reduced140-180 VAC
Frequency45 to 65 Hz
Internal protection16A MCB / rectifier module
Mains terminalTerminal blocks of 10 mm2
AUPUS C 24-6.6AUPUS C 48-9.6AUPUS C 60-9.6AUPUS C 110-9.6AUPUS C 220-9.6
Nominal current10.2 A15.4 A
Maximum current13.8 A19.4 A
Inrush current per rectifier14.7 A18 A
main switch40 A
Recommended mains fuse3 x 25 A
OutputAUPUS C 24-5.5AUPUS C 48-8.0AUPUS C 60-8.0AUPUS C 110-8.0AUPUS C 220-8.0
GroundingFloating+ or floating+ groundedfloatingfloating
Nominal voltage24 VDC48 VDC60 VDC110 VDC220 VDC
Voltage range21-31 VDC42-58 VDC51-72 VDC97-132 VDC189-265 VDC
Ripple noise< 100 mVp-p
Number of rectifierMax 5
Maximum current229A @ 24V164A @ 48V134A @ 60V72A @110V36A @ 220V
Output current200A @ 27.5V147 @ 54.5V117A @ 68.1V65A @ 123.6V33A @ 220V
Power max.5.5 kW8.0 kW
Redundant power4.4 kW6.4 kW
Output terminalsTerminal blocks of 25 mm2
Battery connectionAUPUS C 24-5.5AUPUS C 48-8.0AUPUS C 60-8.0AUPUS C 110-8.0AUPUS C 220-8.0
MCB1 pc 250A1 pc1 pc1 pc1 pc 50A
Optional breakerMax 1 MCB

Load distribution

(options)

AUPUS C 24-5.5AUPUS C 48-8.0AUPUS C 60-8.0AUPUS C 110-8.0AUPUS C 220-8.0
1-pole MCB, 2...63AMax 20 loadsMax 20 loadsMax 20 loadsN/AN/A
2-poles MCB, 2...63AMax 10 loadsMax 10 loadsN/AMax 10 loadsMax 10 loads