DC Power systems in 19" 7U Racks AUPUS C

AUPUS C DC power systems are robust, free convection cooled, N+1 redundant backup power solutions for critical infrastructure applications such as transmission and distribution substations, process industries and telecommunications. 

More details

Features

  • Convection cooling
  • Models for 24, 48, 60, 110, 220 VDC
  • Max 4.8 kW output power
  • N+1 redundancy
  • Battery connection: 1 string with full current, MCB protection

Options: Battery LVD, temperature sensor, wall mounting+ IP21 kit

Product description

AUPUS C DC power systems are robust, free convection cooled, N+1 redundant backup power solutions for critical infrastructure applications such as transmission and distribution substations, process industries and telecommunications.

AUPUS C DC power systems consist of MRC-rectifiers, VIDI+ controllers, connections for mains, battery and load.

General construction
CoolingNatural convection
ProtectionIP20, option IP21
Controller user interfaceDisplay and local control in front panel
Distribution and connectionsBehind front panel
ColorFrame RAL 7012
Dimensions, rack mountingHeight: 311mm, width: 438mm, depth: 451mm
Dimensions, wall mounting+ IP21
Environment and standards
Operating temperature-20°C ... +45°C
Humidity max95% relative humidity, non-condensing
Altitude max2000 m above sea level
SafetyIEC/EN 60950-1
EMCEmissions: IEC/EN61000-6-4, immunity : IEC/EN 61000-6-2, harmonic currents: IEC/EN 61000-3-2, voltage fluctuation and flicker: IEC/EN 61000-3-3
Others options
Wall mounting kit including IP21 drip water cover
NTC temperature sensor
Battery LVD contactors
Controllers: VIDI+ or VIDI+ I/O
InputAUPUS C 24, AUPUS C 48, AUPUS C 60, AUPUS C 110, AUPUS C 220
AC-connection3W + N + PE
Nominal voltage230 / 400 VAC
Range, full180-275 VAC
Range, reduced140-180 VAC
Frequency45 to 65 Hz
Internal protection16A MCB / rectifier module
Mains terminalTerminal blocks of 10 mm2
AUPUS C 24-3.3AUPUS C 48-4.8AUPUS C 60-4.8AUPUS C 110-4.8AUPUS C 220-4.8
Nominal current5.3 A7.7 A
Maximum current6.9 A9.7 A
Inrush current per rectifier< 20 A
main switch40 A
Recommended mains fuse3 x 25 A
OutputAUPUS C 24-3.3AUPUS C 48-4.8AUPUS C 60-84.8AUPUS C 110-4.8AUPUS C 220-4.8
GroundingFloatingFloatingFloatingFloatingFloating
Nominal voltage24 VDC48 VDC60 VDC110 VDC220 VDC
Voltage range21-31 VDC42-58 VDC51-72 VDC97-132 VDC189-265 VDC
Ripple noise< 100 mVp-p
Number of rectifierMax 3
Maximum current137A @ 24V100A @ 48V80A @ 60V44A @110V22A @ 220V
Power max.3.3 kW4.8 kW
Redundant power2.2 kW3.2 kW
Output terminalsTerminal blocks of 25 mm2
Connections
MainsMains switch, 16A MCB and connection terminal
Battery2-pole MCB