Inverters AUPUS EIM

The AUPUS Inverter system has a modular construction. The inverter modules can be combined with static switch, manual bypass, AC distribution and 3-phase synchronization modules based on customer’s needs.

More details

Features

  • Support to 24, 48, 60, 110, 125, 220, 230Vdc nominal battery voltages
  • Standard 19” rack • Small size, light weight
  • Full access from front
  • Remote monitoring
  • High efficiency
  • Hot swap N + 1 redundant system
  • Static switch allows On-line and Off-line modes
  • High overload capability
  • Parallel connectable 1000 VA to 24 kVA
  • 1-phase and 3-phase output

Product description

The AUPUS Inverter system is a redundant, fault tolerant system. Inverter system is optimal solution when long autonomy time and long battery service life are required. Inverter system is compatible with several battery configurations. Inverter system fits in the standard 19” racks and cabinets. EIM inverters efficiencies are high, up to 90%.

The AUPUS Inverter system has a modular construction. The inverter modules can be combined with static switch, manual bypass, AC distribution and 3-phase synchronization modules based on customer’s needs.

The AUPUS Inverter system can be integrated in the same cabinet as Aunilec DC power systems with advanced VIDI+ controller, temperature sensors and battery monitoring.

Technical specifications, manual bypass and AC distribution

Electrical
Operational voltage range100-240 VAC
Power rating6000VA, max 30A
Bypass switch4 pole (OFF, mains, sync, auto) manual bypass rotating switch
AC distributionThree (3) MCBs, standard configuration: 1pc B6A, 1pc B10A, 1 pc B32A
Mechanical
Dimensions14 TE x 6U x 160 mm
Screw terminals6 mm2 or 10 mm2 for mains in and load. 90 cm cable set for static switch
EnclosureSteel casing IP20
Environmental
Operating temperature-25...+50°C full power, +45...+60°C reduced power
Standards
SafetyEN60950-1
EMCEN55022B, EN61000-6-3, EN61000-6-2, EN61000-6-1
Electrical
Input voltage, nominal24VDC48/60VDC110/125VDC220/230VDC
Output power1000VA1200VA1000VA1200VA1000VA1200VA1000VA1200VA
Input voltage range20-32VDC40-72VDC88-150VDC178-275VDC
Input current, max continuous37A50A22A35A10A16A5A8A
Input current, max 5 sec peak75A75A50A50A22A22A11A11A
Inrush current<30A<20A<10A<10A
Output voltageNominal 230VAC sine wave, user programmable 200-240V, floating output
Output frequencyNominal 50Hz, user programmable 40-70Hz
Nomonal output power1000VA, 600W1200VA, 800W1000VA, 700W1200VA, 1200W1000VA, 700W1200VA, 1200W1000VA, 700W1200VA, 1200W
Overload, 5s1200W1700W1700W1700W
Overload, 60s110% for all models, max time can be limited shorter. Number of restart attemps and delays are user programmable
Output current, nominal4,4A5,2A4,4A5,2A4,4A5,2A4,4A5,2A
Max short circuit current, 1-4 sec13A
Efficiency83%90%
Load power factor rangeFull power rating from 0 inductive to 0 capacitive
THD, resistive laod<2%
Crest factor>3>2,7>3>2,7>3>2,7>3>2,7
Static regulation 0...100% load+/-3%
Psophometric noise, input<2mV
Isolationinput-chassis 1500Vca (2000 Vcc), input-output 3000Vca (4000Vcc), output chassis 1500Vca (2000Vcc)
Protectionoutput current limiting, overload and short circuit proof. Internal input and output fuses
DC input fuse (external fuse needed)max C 63Amax C 40Amax C 25Amax C 16A
Alarms, indications and controls
LED-indicationsInput ON, output ON, output overloading, 4 levels; overload/fault
Relay alarms2 relay contacts
Remote monitoring

Web interface, SNMP traps, SMTP mail alerts and Modbus TCP/IP through VIDI+ controller.

Status information: for example input and output voltage, power, temperature, fault, etc.

Parameter adjustement: limits, output voltage, overload, fault, etc.

Environmental
Operating temperature / humidity0...+45°C full power0...+45°C full power-10...+45°C full power-10...+45°C full power
CoolingNatural convectionFan coolingNatural convectionFan coolingNatural convectionFan coolingNatural convectionFan cooling
AltitudeFull power up to 2000m, derating -2%/100m, max altitude 3000m
Mechanical
Dimensions14TE x 6U x 372 mm
Connectors in front panel

Input DC connector : Anderson SB506331 G4

Output: finger protected AC-connector, Wieland ST18/3S2

EnclosureSteel casing IP20
Standards
SafetyEN60950-1
EMC48/60VDC inverters: EN55022B, EN61000-6-3, EN61000-6-2, ETS 300 132-2

Technical specifications, static switch module

Electrical
Operational voltage range80-270VAC
Synchronized frequency range40-70Hz (user programmable)
ProtectionExternal fuse in mains AC input
Efficiency> 99% @ 230 VAC, full power
Alarms, indications and controls
LED-indicationsOverload - fault-mains failure - mains in use - inverter failure - inverter in use - synchronized - communication
Relays alarmsFault in system - primary supply failure
Remote monitoring

Web interface, SNMP traps, SMTP mail alerts and Modbus TCP/IP through VIDI+ controller.

Status information: for example input and output voltage, power, temperature, fault, etc.

Parameter adjustement: limits, output voltage, overload, fault, etc.

Mechanical
Dimensions

14TE x 6U x 372 mm

Connectors in front panel

inverters up to 5 pcs ST18AC input

AC input AMP Mate-N-Lock AC output

AC output AMP Mate-N-Lock

EnclosureSteel casing IP20
Environmental
Operating temperature0...+45°C full power, +45...+60°C reduced power
Standards
SafetyEN60950-1
EMCEN55022B, EN61000-6-3, EN61000-6-2, EN61000-6-1